T/CES 267-2023 High-voltage AC circuit breaker latent fault monitoring device technical specification
T/CES 267-2023 High-voltage AC circuit breaker latent fault monitoring device technical specification
Basic Information
Scope
Scope: This standard specifies the composition and monitoring methods, technical requirements, test methods, inspection rules, etc. of the latent fault monitoring device for high-voltage AC circuit breakers (hereinafter referred to as the device). This standard applies to the design, manufacture, testing, selection, and operation of latent fault monitoring devices for high-voltage AC open-type circuit breakers of 10kV and above; Main technical contents: This document specifies the composition, monitoring functions, technical requirements, test methods, inspection rules, marking, packaging, transportation, and storage of latent fault monitoring devices for high-voltage circuit breakers. This document proposes the following technical indicators: 1. The acceleration measurement error of the vibration sensor shall not exceed ±1% of the full scale, and the actual effective bits of the analog-to-digital converter for vibration signal acquisition shall not be less than 14 bits; 2. The electric field sensor shall be able to measure electric field strengths of 0.1 kV/m to 20 kV/m; the electric field sensor shall be able to identify electric field changes of 30 V/m per millisecond, and the measurement accuracy shall be better than 0.01 kV/m; 3. The current sensor shall be able to measure currents of 1 mA to 2 A. The measurement error of the current sensor shall not exceed ±2‰ of the full scale; the synchronization error of the current phase angle collected by multiple sensors shall be less than 5°.