GB/T 37751.32-2019 Active National standards

GB/T 37751.32-2019 Residual current operated circuit-breakers for household and similar use—Part 3-2:Particular requirements for RCDs with flat quick-connect terminations

GB/T 37751.32-2019 Residual current operated circuit-breakers for household and similar use—Part 3-2:Particular requirements for RCDs with flat quick-connect terminations

Publish Date: 2019-06-04 Implement Date: 2020-01-01 For services related to genuine standard inquiry, procurement, translation, and other related services in China, please Contact Us

Basic Information

Standard Code: GB/T 37751.32-2019
Standard Type: National standards
Standard Status: Active
is_force_gb: no
CCS Name: Low-voltage distribution electrical equipment
ICS Name: Fuses and other overload protection devices
Publish Date: 2019-06-04
Implement Date: 2020-01-01
Pages: 11 pages

Scope

This part of GB/T 37751 is applicable to RCDs with flat quick-connect terminals. The terminal consists of an insertion-type connection piece with a nominal width of 6.3 mm and a thickness of 0.8 mm (see 3.2), and a matching socket connector, which is used to connect electrical copper wires according to the manufacturer's instructions, with a rated current of less than or equal to 16 A.
This part cannot be used alone. It needs to be used together with the RCD product standard (IEC 61008-1 or IEC 61009-1) for RCDs with flat quick-connect terminals.
The electrical copper wires that can be connected are soft wires with a cross-sectional area of 4 mm2 or less, or hard wires with a cross-sectional area of 2.5 mm2 or less (AWG wire gauge equal to or greater than 12).
This part is specifically suitable for RCDs where the insertion-type connection piece is an integral part.

Development Information

Word Count: 20 Thousand words Pages: 11 pages

Same series standard

Referenced Standards

IEC 61008-1 IEC 61009-1 IEC 61210 IEC 62873-2

Adopt standards

IEC 62873-3-2:2016

Related Standards