GB/T 14420-2024 Analysis of water used in boiler and cooling system—Determination of chemical oxygen demand—Rapid method with potassium dichromate
GB/T 14420-2024 Analysis of water used in boiler and cooling system—Determination of chemical oxygen demand—Rapid method with potassium dichromate
Basic Information
Scope
This document describes the method of determining the chemical oxygen demand (COD Cr) in boiler water and cooling water using the rapid method of potassium dichromate.
The volumetric method described in this document is suitable for determining the chemical oxygen demand (COD Cr) in boiler water and cooling water ranging from 10 mg/L to 1,000 mg/L (calculated as oxygen); the spectrophotometric method and the rapid spectrophotometric method are suitable for determining the chemical oxygen demand (COD Cr) in boiler water and cooling water ranging from 15 mg/L to 1,000 mg/L.
This document is also applicable to the determination of chemical oxygen demand (CODCr) in surface water, groundwater, domestic wastewater, and industrial wastewater.